Belt Drive

Standard Ratings Cooling Capacity
Unit Size Rated CFM Rows EWT Total Cooling (MBH) Sensible Cooling (MSH)
008 800 4 4038.2125.36
4530.0922.01
5022.2519.00
6 4047.3329.45
4538.2025.36
5028.6321.44
8 4050.1930.81
4540.5626.39
5030.2322.07
012 1200 4 4055.7437.38
4543.5232.38
5031.7727.91
6 4069.9543.67
4556.2037.58
5041.8631.74
8 4075.3146.22
4560.8939.60
5045.3433.11
016 1600 4 4076.7850.89
4560.2844.07
5044.2937.93
6 4092.4857.86
4574.0149.71
5054.6641.86
8 40102.8362.80
4583.8253.96
5063.1945.24
020 2000 4 4099.5766.16
4578.1756.21
5057.0848.04
6 40113.2871.27
4589.7360.97
5065.2951.16
8 40127.1177.81
45103.0366.68
5076.8755.70
030 3000 4 40143.9695.42
45113.5282.83
5083.8771.42
6 40175.59109.49
45141.2494.26
50105.3979.63
8 40193.52118.11
45158.00101.55
50119.4785.23
040 4000 4 40180.11122.04
45142.39106.72
50106.4693.06
6 40228.80143.56
45184.56124.08
50139.09105.60
8 40249.44153.26
45202.80131.94
50153.13111.16
050 5000 4 40222.94151.56
45173.35132.68
50132.25115.94
6 40279.75176.73
45224.92152.65
50169.70130.15
8 40306.33188.97
45248.35162.67
50187.21137.27
060 6000 4 40272.77184.13
45216.24161.09
50162.39140.55
6 40335.09211.70
45269.26182.92
50202.22155.91
8 40373.35229.50
45303.71197.69
50229.86166.80
080 8000 4 40354.54241.58
45280.44211.61
50210.47185.08
6 40439.57279.04
45352.48241.15
50264.33205.83
8 40492.47303.46
45399.89261.38
50302.11220.66
100 10000 4 40465.38311.38
45370.53272.43
50278.98237.27
6 40551.78349.84
45442.68302.31
50332.13257.90
8 40617.50380.23
45502.10327.70
50379.85276.70
120 12000 4 40525.98359.74
45415.94315.36
50312.07276.06
6 40659.12418.44
45529.00361.82
50397.26309.02
8 40723.97448.23
45585.72385.95
50440.86326.10

Notes: Based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F temperature rise. Motor voltage 115/1/60 power source. Air flow under dry coil conditions. Water pressure drops shown in feet of water. All units are listed under UL Category Control No. LZFE.