Superior Performance

Heating Performance
Size Motor Type Coil Rows/(FPI) Rated CFM MBH GPM WPD
(FT./H2O)
004 (Standard) 1 Row (12) 470 18.8 0.9 1.2
2 Rows (12) 470 29.8 1.5 0.9
006 (Standard) 1 Row (12) 520 21.8 1.1 1.4
2 Rows (12) 520 35.5 1.8 1.1
(High Static) 1 Row (12) 665 18.8 0.9 1.0
2 Rows (12) 665 31.8 1.6 0.8
008 (Standard) 1 Row (12) 770 24.5 1.2 1.6
2 Rows (12) 770 40.8 2.0 1.3
(High Static) 1 Row (12) 855 25.8 1.3 1.7
2 Rows (12) 855 43.4 2.2 1.4
010 (High Static) 1 Row (12) 1,010 33.9 1.7 3.0
2 Rows (12) 1,010 55.8 2.8 2.3
012 (High Static) 1 Row (12) 1,250 38.4 1.9 0.8
2 Rows (12) 1,250 68.3 3.4 2.0
015 (High Static) 1 Row (12) 1,580 49.6 2.5 1.3
2 Rows (12) 1,580 85.9 4.3 3.1
018 (High Static) 1 Row (12) 2,005 62.1 3.1 1.9
2 Rows (12) 2,005 107.3 5.4 4.8
022 (High Static) 1 Row (12) 2,285 72.2 3.6 2.6
2 Rows (12) 2,285 124.4 6.2 6.5

Notes: Based on 70°F DB EAT, 180°F EWT, 40°F temperature drop, high fan speed. Motor voltage 115/1/60 power source. Air fl ow under dry coil conditions. Water pressure drops shown in feet of water.