Vertical Stack

Approval ratings in accordance with Industry Standard 440 for Equipment Testing and Rating of Fan Coil Air Conditioners
Unit Size (1) Rated CFM (2) Cooling Capacities (3) Motors Filters(6)
L x W (In)
Min. Free Area
GPM PD (4) SENS Heat MBH Total Heat MBH Amps Watts RPM (High) Inlet Sq. In. Outlet Sq. In.
003-1A 320 1.9 10.85 6.6 9.2 .90 95 1070 12 x 24 126 113
003-2 310 2.4 7.7 7.6 11.5

004-1A 430 2.5 18.9 8.8 12.2 1.05 104 1065
004-2 400 3.2 29.6 10.0 15.5

006-1A 640 3.6 16.2 13.0 17.5 1.90 180 800 16 x 20 165 141
006-2 600 4.6 29.0 15.5 22.5

008-1A 820 4.9 32.6 17.5 23.5 2.50 250 825
008-2 800 6.2 20.5 21.2 30.5

010-1A 1000 5.8 31.7 20.0 28.0 3.50 360 800
010-2 940 7.0 25.0 24.0 34.0

Notes:

(1) Capacity ratings apply to all models.

(2) Air flow under dry coil conditions. Inlet air 70-80°F Dry Bulb.

(3) Based on inlet air 80°F Dry Bulb and 67°F Wet Bulb. Water inlet at 45°F, water outlet at 55°F.

(4) Pressure drop shown in feet of water. Maximum average water temperature 50°F.

(5) Permanent split capacitor motor at high fan speed.

(6) Throw away filter is 1" thick.